Configure the auto integrity update interval of Publisher - Subscriber (PubSub) Manager
- Last UpdatedApr 24, 2025
- 1 minute read
Note: For information on overriding default configuration settings, refer to Modify configuration settings.
Follow this procedure to configure how often the system performs an auto integrity update for the PubSub Manager.
To configure the auto integrity update interval of Publisher - Subscriber (PubSub) Manager
-
In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_alarmbracket.json file.
-
In the following line, change the numerical value to the desired value (in minutes):
{
"RealTime": {
"ALMB_PS_INTEG_INTERVAL": 300,
"ALMB_MON_PROC_INTERVAL": 15,
"ALMB_PS_PRINT_INTERVAL": 1800
}
}
-
Save the file.
-
Restart the RealTime service.