ActionSequence table details
- Last UpdatedApr 24, 2025
- 2 minute read
The actionSequence table is used by the Action Sequence subsystem to store configuration and runtime data for action sequences. The actionSequence table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
convert_item_grp |
agaConvertItemGrpslot |
The name of the aga_convert_item_grp record with which the aga_convert_item record will be grouped. |
|
convertValue |
double |
The corresponding Remote Terminal Unit (RTU) value of the itemValue. |
|
dataset |
doas_dset_slot |
This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record. |
|
description |
description |
A description of what this action sequence does, up to 47 characters in length. |
|
flag.alminh |
oas_boolean_t |
Prevent alarms from being generated when a sequence fails to complete successfully? |
|
flag.bmsg |
messageslot |
The message associated with the record. |
|
flag.cevinh |
oas_boolean_t |
Prevent events from being generated when a sequence has successfully completed, or when a Controller stops a sequence? |
|
flag.clrinh |
oas_boolean_t |
Prevent alarms from being generated when a sequence has successfully completed? |
|
flag.evtinh |
oas_boolean_t |
Prevent events from being generated when a sequence fails to complete successfully? |
|
flag.priorityDisplay |
modelname |
The display associated with the Priority Display icon on an easy eXtended Operator Station (ezXOS) Control dialog. |
|
flag.safety |
oas_boolean_t |
Is the point safety-related? |
|
group |
groupslot |
This field shows the group that this point is associated with for alarming. |
|
inh.admin |
oas_boolean_t |
Inhibit the actionSequence record? The Controller will be prevented from making the record active. |
|
inhibits.failBranch.alinh |
oas_boolean_t |
Prevent alarms from being generated when a step in a sequence fails, but a failure branch exists and is started? |
|
inhibits.failBranch.evtinh |
oas_boolean_t |
Prevent events from being generated when a step in a sequence fails, but a failure branch exists and is started? |
|
inhibits.sequenceStepEvt |
oas_boolean_t |
Prevent the event recording that occurs as a result of the completion of individual steps? |
|
itemValue |
double |
The value of the American Gas Association (AGA) parameter within Measurement. |
|
name |
pntname |
The name of the actionSequence record. |
|
twoStageActivationEnabled |
oas_boolean_t |
Enable two-stage activation? |