To help with modem configuration, sample modem record configuration details are provided for the Motorola V.3600 series modem and U.S. Robotics Sportster modem.

Modem records are configured only for modems at the host end that must dial to obtain a connection to one or more remotes. Much of the information required for a dial connection resides in the modem record.

The tables below provide sample configuration details for a Motorola V.3600 Series modem and U.S. Robotics Sportster modem. A modem record must be configured to reflect the particular type of modem that is used.

Note: For commands specific to the modem you are using, refer to the manual provided with the modem.

Sample modem command configuration - U.S. Robotics Sportster

String to Be Sent

Description

Message OK String

Format

Timeout

Connect

ATH0\015\012

Hang up

OK

Command

8000

ATE0\015\012

Don’t echo local characters

OK

Command

3000

AT&C1&D2\015\012

Set local modem characteristics:

  • DCD on while carrier is present (&C1)

  • DTR off causes disconnection (&D2)

OK

Command

1500

ATDT%s\015\012

Dial (using tone rather than pulse)

CONNECT

Telno

8000

Disconnect

ATH0\015\012

Hang up

OK

Command

8000

Check

ATO\015\012

Force modem into data mode (as opposed to command mode)

CONNECT

Command

8000

Sample modem command configuration (Motorola V.3000 Series)

String to Be Sent

Description

Message OK String

Format

Timeout

Connect

ATH\015\012\0

Hang up

Command

5000

ATE&C1&D2\015\012\0

Set local modem characteristics:

  • Local character echo off (E)

  • DCD on while carrier is present (&C1)

  • DTR off causes disconnection (&D2)

OK

Command

1500

ATDT%s\015\012\0

Dial (using tone rather than pulse).

CONNECT

Telno

100

Disconnect

ATH\015\012\0

Hang up

OK

Command

8000

Check

ATO\015\012\0

Force modem into data mode (as opposed to command mode)

CONNECT

Command

5000