AVEVA Enterprise SCADA

Data types

  • Last UpdatedApr 24, 2025
  • 1 minute read

The Open Platform Communications (OPC) client protocol supports seven different data types and supports conversion between different data types.

The following table lists the data types supported by the OPC client protocol:

OPC Client protocol data type

Database

Analog

Status

Rate

Multistate (Bit Format)

Boolean

N/A

Read/Write

N/A

Read/Write

Unsigned 16 bit (UI2)

Read/Write

Read

Read

Read

Signed 16 bit (I2)

Read/Write

Read

Read

Read

Unsigned 32 bit (UI4)

Read/Write

Read

Read

Read

Signed 32 bit (I4)

Read/Write

Read

Read

Read

Float (R4)

Read/Write

N/A

Read

N/A

Double (R8)

Read/Write

N/A

Read

N/A

Data Type Conversion

The OPC server allows conversion between the following data types:

From/To

BOOL

I1

UI1

I2

UI2

I4

UI4

R4

R8

BOOL

OK

!

!

!

!

!

!

!

!

I1

OK

OK

!

!

!

!

!

!

!

UI1

OK

OK

OK

!

!

!

!

!

!

I2

OK

OK

OK

OK

!

!

!

!

!

UI2

OK

OK

OK

OK

OK

!

!

!

!

I4

OK

OK

OK

OK

OK

OK

!

!

!

UI4

OK

OK

OK

OK

OK

OK

OK

!

!

R4

OK

OK

OK

OK

OK

OK

OK

OK

!

R8

OK

OK

OK

OK

OK

OK

OK

OK

OK

Legend:

OK – conversion is valid

! – indicates possible overflow. In case of overflow, the target value is not changed.

(OPC Data Access Custom Interfaces specification 2.05).