Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Open Platform Communications (OPC) data quality calculation

Open Platform Communications (OPC) data quality calculation

  • Last UpdatedApr 24, 2025
  • 1 minute read

The Open Platform Communications (OPC) DA server calculates the data quality of each of the supported points, based on the OPC Data Quality Truth table. For all tables (Analog, Rate, Status, Tank, and Multistate):

  • Flag.severity

  • Flag.alarm

  • Flag.alminh

  • Flag.error

  • Flag.offscan

  • Flag.tag

  • Flag.fresh

  • Flag.manl

  • Flag.msgtxt

  • lastKrunchTime

Analog specific fields:

  • Curval

Status specific fields:

  • Cursta

Rate specific fields:

  • Curate

  • Accur

Tank specific fields:

  • field.volume

  • field.num_inc

  • currentGO.volume

  • currentGO.num_inc

  • currentGS.volume

  • currentGS.num_inc

  • flevel

  • GOflow_rate

  • GSflow_rate

Multistate specific fields:

  • inputCurRaw

OPC Data Quality Truth Table

AVEVA Enterprise SCADA Quality Data

OPC Quality

flag.fresh

flag.manl

Quality Enumeration

NO

NO

LAST_USABLE

NO

YES

LOCAL_OVERRIDE

YES

YES

LOCAL_OVERRIDE

YES

NO

GOOD

Related Links