Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Enter the results of Point to Point Verification

  • Last UpdatedApr 24, 2025
  • 3 minute read

Perform this procedure to check if the value of a point displayed in AVEVA Enterprise SCADA differs from the value recorded by the field instrument.

Before you begin

Complete the steps in Open the Point Verification Control dialog box.

  1. Configure the various fields on the Point Verification Control dialog box, using the table below as a guide.

  2. Do one of the following:

    • To save the record in a pending state, refer to Create a pending record.

    • To submit the record, refer to Save verification information to the database.

      Embedded Image (65% Scaling) (LIVE)

      Item

      Description

      Address

      The point's input/output coordinates.

      As noted above, you must configure this field for multistate points.

      Verified

      This field indicates whether or not the data currently displayed on the Point Verification Control dialog box exists in the CRM database in a "verified" state.

      Verification Reason

      The reason for verification.

      Options:

      • Display Change

      • SCADA Database Change

      • PLC/RTU Field Device Change

      • Initial Commissioning

      Verification Date

      One of the following:

      • The date on, and local time at, which point verification results for the record were last submitted to the CRM database.

      • Today's date and the current, local time after you select New to enter new results.

        Note: In the event of a change to the time zone setting, the new setting only takes effect after the restart of the easy eXtended Operator Station (ezXOS).

      Field Location

      The name of the associated station (station record).

      Equipment Description

      The record's point class.

      Physical Location

      The physical location of the point.

      Phys. Loc. Verified By

      The name* of the person who verified the Physical Location.

      SCADA Value

      The point's current value.

      Recorded SCADA Value

      Select Capture to copy the point's current value from the SCADA Value field into one of the three Recorded SCADA Value fields. Modify the value as desired.

      When you verify the record, the application saves the Recorded SCADA Value field values to the CRM database.

      Field Value

      Record the current field value into one of the three Field Value fields to correspond with the Recorded SCADA Value fields.

      Commanded

      Select this check box if verification is done by issuing a command to the field device.

      Feedback

      Select this check box if verification is done using a feedback point in the field device.

      Scaled Value

      Select this check box if the Field Value uses a different scaling value from the SCADA Value.

      Calibration

      Select this check box if commissioning is being performed during a calibration task. Selecting this check box enables the "As Found" Value and "As Left" Value fields.

      Simulated

      Select this check box if some method other than reading the actual value is used to perform the test.

      Simulation Reason

      Record the reason for simulating the SCADA Value.

      "As Found" Value

      The current value of the point prior to calibration.

      "As Left" Value

      The current value of the point after calibration.

      SCADA Verified

      The name of the user logged on to the system.

      Field Verified

      The name* of the person responsible for retrieving the field value entered in the Field Value field.

      Approved By

      The name* of the person who approved the Field Value.

      Safety Point

      This field indicates whether or not the point is safety related.

      For further information, refer to Safety points.

      Alarms Test Method

      A brief description of the method used to test alarms on this point.

      MOC #

      The number of the maintenance system containing commissioning or calibration information.

      Reference #

      The reference number associated with this verification record.

      Comments

      Comments about this verification record.

      Remove From Test Mode Sets

      If selected when Verify is selected, then the point that is being verified will be automatically removed from any test mode sets that it is contained in, and the point is taken out of test mode.

      *Any available names in the Phys. Loc. Verified By, Field Verified, and Approved By fields come from the On Call database if your system is configured with the On Call database. Any name can be entered into these fields regardless of what names appear in the dropdown menu. For further information, refer to On Call.

      Note: The names are stored independent of the On Call database. If, for example, an employee leaves the company, an Administrator will likely remove his name from the On Call database. The former employee's name, however, remains attached to the results submitted to the CRM database.