Use the Commands tab in the modem Row Edit dialog box to configure the connect, disconnect and check commands for the modem. It is used for both dial and cryout.
-
Connect Commands. The fields in this area enable the connect configuration set, which allows you to configure commands for connecting a modem. This is used for dial and cry out To ensure that the modem is hung up before connection is attempted, the first connection string (for example, String to Be Sent) must always be the hang-up sequence (for example,, ATH\015\012\0). This ensures that the host-swapping of modems and service/system failovers work properly.
-
Disconnect Commands. The fields in this area enable the disconnect configuration set, which allows you to configure commands for disconnecting a modem. This is used for dial and cryout.
-
Check Commands. A no reply response is a loss of carrier or dial connection. The field in the check command-area enables the check configuration set, which is used when a no reply response is received from a remote. This is used for dial only. For more information on valid commands, refer to the modem’s command manual.
Refer to the table below for field descriptions and instructions on how to configure the editable fields.

Items on the Command Tab in the modem Row Edit Dialog Box
|
Items |
Description |
|---|---|
|
String to Be Sent |
Enter the string to send to the modem. It contains characters such as: <CR> (\015), <LF>(\012) and the end-of-string indicator (\0). Examples: This command puts a Hayes-compatible modem in command mode: +++\0 This command tells a Hayes-compatible modem to hang up: ATH\015\012\0 |
|
Message OK String |
(Optional) Enter the expected response from the modem. Example: OK OK is a normal response to many commands. |
|
Format |
Select one of the following formats:
|
|
Timeout |
Enter the maximum time, in milliseconds, to wait for an expected response. For a Telno format, this delay is added to the additional wait time for auto answer to give the overall delay time. For a Delay format, the Timeout: column specifies the duration of the delay. Typically, the Delay format is used after setting the connect configuration set’s Telno format and the check configuration set’s "ATO" string to 1 or 2 seconds. |