FlowTotalConfig table details

  • Last UpdatedApr 24, 2025
  • 4 minute read

The flowTotalConfig table is used to store point totals and calculation elements used by the Flow Total application. The flowTotalConfig table contains the following internal fields:

Internal Field Name

Data Type

Description

accessFlag

varchar

The display accessing this record.

activeAlmLimit_[0-3]

varchar

The associated active alarm limit for totalBlock[0-3], respectively.

almLimitSet[0-3]

almlimitsetslot

The name of the almlimitset record that uses the alternative alarm limits configured in the almlimit record.

dataset

doas_dset_slot

This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record.

description

description

A description of this flowTotalConfig point, up to 47 characters in length.

displayOrder

int

The display order of the record.

dsysControl

varchar

Indicates if the local system is in control of this remote.

enabled

oas_boolean_t

Have the Monitor process calculate values for the flowTotalConfig record's associated elements?

flag

flags

For information on the flag structure, see Flag structure details.

group

groupslot

This field shows the group that this point is associated with for alarming.

lastTime

int

The last time the record was krunched.

lastTime.high

int

The last time the record was krunched (displayed in high order by seconds).

lastTime.low

int

The last time the record was krunched (displayed in low order by milliseconds).

mappingFlag

unsigned int

The 32-bit integer value used to map this point to a non-AVEVA Enterprise SCADA system.

name

pntname

The unique name of this flowTotalConfig record. The name can be up to 32 characters in length.

pointClass

configenumslot

The Point Class category contains multiple configuration enumerations used for categorical configuration of points.

pointSubClass

configenumslot

Point Sub Class is a configurable enumeration category used for categorical configurations, but you cannot use this for configurable alarms and events.

priority

exec_order

The priority of calculation (execution order) of the flowTotalConfig record.

ptnum

int

The slot number in the database.

safetyPtState[0-49].Condition

varchar

The safety condition of the state.

stateInhibit.inh_dev

oas_boolean_t

Inhibit Creep state alarming?

stateInhibit.inh_flat

oas_boolean_t

Inhibit Flatline state alarming?

stateInhibit.inh_hi

oas_boolean_t

Inhibit High state alarming?

stateInhibit.inh_hihi

oas_boolean_t

Inhibit HighHigh state alarming?

stateInhibit.inh_lo

oas_boolean_t

Inhibit Low state alarming?

stateInhibit.inh_lolo

oas_boolean_t

Inhibit LowLow state alarming?

stateInhibit.inh_roc

oas_boolean_t

Inhibit Rate of Change state alarming?

stateInhibit.inh_uhi

oas_boolean_t

Inhibit User High state alarming?

stateInhibit.inh_ulo

oas_boolean_t

Inhibit User Low state alarming?

station

stationslot

The name of the associated station record.

totalBlocks.totalBlock[0-3].ana_rate

analogslot

The name of the analog record used as a rate in the Offscan Integration equation.

totalBlocks.totalBlock[0-3].avg.doit

oas_boolean_t

Have the Monitor process calculate the average value for the element?

totalBlocks.totalBlock[0-3].creep.devlim

float

The maximum deviation value (EGUs) that is acceptable before calibration deteriorates.

totalBlocks.totalBlock[0-3].creep.doit

oas_boolean_t

Enable Creep Detection alarming?

totalBlocks.totalBlock[0-3].doTod

oas_boolean_t

Roll over the flowTotalConfig record at the totalBlocks[0-3].Tod hour?

totalBlocks.totalBlock[0-3].enabled

oas_boolean_t

Enable calculation of this element's value?

totalBlocks.totalBlock[0-3].engrunit.egumax

float

The highest measurable value of the instrument in engineering units (EGUs).

totalBlocks.totalBlock[0-3].engrunit.egumin

float

The lowest measurable value of the instrument in EGUs.

totalBlocks.totalBlock[0-3].flag.alminhconfig

oas_boolean_t

Inhibit off-normal alarming?

totalBlocks.totalBlock[0-3].flag.cevinh

oas_boolean_t

Inhibit normal logging?

totalBlocks.totalBlock[0-3].flag.clrinhconfig

oas_boolean_t

Inhibit normal alarming?

totalBlocks.totalBlock[0-3].flag.evtinh

oas_boolean_t

Inhibit off-normal logging?

totalBlocks.totalBlock[0-3].flag.priorityDisplay

modelname

The display associated with the Priority Display icon on an easy eXtended Operator Station (ezXOS) Control dialog.

totalBlocks.totalBlock[0-3].flags.bsmg

messageslot

The message associated with the element.

totalBlocks.totalBlock[0-3].hilow.dead

float

The alarm deadband value for the flowTotalConfig point.

totalBlocks.totalBlock[0-3].hilow.deltatime

long

The time interval over which the system should calculate the Rate of Change (ROC).

totalBlocks.totalBlock[0-3].hilow.doitflat

oas_boolean_t

Enable Flatline Alarming?

totalBlocks.totalBlock[0-3].hilow.doithi

oas_boolean_t

Enable the High alarm limit?

totalBlocks.totalBlock[0-3].hilow.doithihi

oas_boolean_t

Enable the HighHigh alarm limit?

totalBlocks.totalBlock[0-3].hilow.doitlo

oas_boolean_t

Enable the Low alarm limit?

totalBlocks.totalBlock[0-3].hilow.doitlolo

oas_boolean_t

Enable the LowLow alarm limit?

totalBlocks.totalBlock[0-3].hilow.doitroc

oas_boolean_t

Enable ROC alarming?

totalBlocks.totalBlock[0-3].hilow.doituhi

oas_boolean_t

Enable the user-defined High alarm limit?

totalBlocks.totalBlock[0-3].hilow.doitulo

oas_boolean_t

Enable the user-defined Low alarm limit?

totalBlocks.totalBlock[0-3].hilow.flattimeout

unsigned short

The maximum about of time (minutes) that can pass without the flowTotalConfig value changing.

totalBlocks.totalBlock[0-3].hilow.hihilim

float

The HighHigh alarm limit for the flowTotalConfig point.

totalBlocks.totalBlock[0-3].hilow.hilim

float

The High alarm limit for the flowTotalConfig point.

totalBlocks.totalBlock[0-3].hilow.lolim

float

The Low alarm limit for the flowTotalConfig point.

totalBlocks.totalBlock[0-3].hilow.lololim

float

The LowLow alarm limit for the flowTotalConfig point.

totalBlocks.totalBlock[0-3].hilow.negroclim

float

The maximum, negative allowable ROC (EGUs per second).

totalBlocks.totalBlock[0-3].hilow.roclim

float

The maximum, positive allowable ROC (EGUs per second).

totalBlocks.totalBlock[0-3].hilow.roc_method_used

ROC_method

The type of ROC alarming to use.

totalBlocks.totalBlock[0-3].hilow.uhi

float

The user-defined High alarm limit for the flowTotalConfig point.

totalBlocks.totalBlocks[0-3].hilow.ulo

float

The user-defined Low alarm limit for the flowTotalConfig point.

totalBlocks.totalBlocks[0-3].intg.doit

oas_boolean_t

Have the Monitor process calculate the total quantity (for example, volume) over a given time period?

totalBlocks.totalBlocks[0-3].intg_enable

oas_boolean_t

Have the Monitor process calculate the total quantity when one of the associated data sources goes offscan?

totalBlocks.totalBlocks[0-3].intg.scale

float

The factor used to scale the accumulated quantity.

totalBlocks.totalBlocks[0-3].stateInhibit.inh_dev

oas_boolean_t

Inhibit Creep alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_flat

oas_boolean_t

Inhibit Flatline alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_hi

oas_boolean_t

Inhibit High alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_hihi

oas_boolean_t

Inhibit HighHigh alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_lo

oas_boolean_t

Inhibit Low alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_lolo

oas_boolean_t

Inhibit LowLow alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_roc

oas_boolean_t

Inhibit ROC alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_uhi

oas_boolean_t

Inhibit User High alarming?

totalBlocks.totalBlocks[0-3].stateInhibit.inh_ulo

oas_boolean_t

Inhibit User Low alarming?

totalBlocks.totalBlocks[0-3].Tod

int

The hour of the day at which to roll over the flowTotalConfig record.

totalBlocks.totalBlocks[0-3].unit

units

A text string that describes the EGUs that are measured by this point.

useAlmLimitSet[0-3]

oas_boolean_t

Associate the flowTotalConfig point with alternative alarm limits?

watchdog

varchar

The point staled by the Flatline Watchdog application.

wellunit

varchar

The well unit name.