Remote Row Edit: Alarming tab
- Last UpdatedApr 24, 2025
- 2 minute read
Use the Alarming tab in the remote Row Edit dialog box to configure parameters associated with Re-Alarming and Email Alarm Notification.
Refer to the table below for field descriptions and instructions on how to configure the editable fields.

Items on the Alarming Tab in the remote Row Edit Dialog Box
|
Items |
Description |
|---|---|
|
Enable Realarm (0-255 mins) |
Enter the number of minutes after which an acknowledged alarm should re-alarm. Note: An entry of 0 disables the Re-Alarming functionality. For further information, refer to Re-Alarming. |
|
Enable Email Notification |
Select to enable the record for email alarm notification. For further information on the items in this section, refer to Email Alarm Notification. |
|
Alternate Email Subject |
Select if alarms associated with this point are AVEVA Enterprise SCADA-related alarms. When selected, the subject line of email messages sent to defined recipients comes from the "emailSubject" application record. If the "emailSubject" application record does not exist, the subject line defaults to SCADA Alarm. When not selected, the subject line comes from the "emailMeaSubject" application record. If the "emailMeaSubject" application record does not exist, the subject line defaults to Measurement Alarm. For further information, refer to Email Alarm Notification. |
|
Email Alert Group |
Enter or select the name of the alertGroup record containing the Controllers and/or Administrators who will receive messages about alarms associated with this point. |
|
Minimum Alarm Severity |
Do one of the following:
|
|
Return to Normal Alarms |
Select to generate an email message in the event of a Return-to-Normal alarm. |
|
No Reply Alarms |
Select to generate an email message in the event of a No Reply alarm. |
For further information, refer to Re-Alarming.