AlmSevOverride Row Details: Main tab
- Last UpdatedApr 24, 2025
- 2 minute read
Use the Main tab in the almSevOverride Row Details dialog box to configure both the main properties of the record and alarm matching criteria.
The Alarm Override feature will only consider a record for processing if the alarm matches all configured Alarm Matching Criteria.
Refer to the table below for field descriptions and instructions on how to configure the editable fields.

|
Item |
Description |
|---|---|
|
Description |
Enter a description of the record. The Description can be up to 47 characters in length. This field is for information purposes only and can be used to describe the record, its association with other records, or any other textual information. |
|
Record Number |
This is a non-editable field containing the record slot number in the almSevOverride table. |
|
Alarm Message Regex |
In the Alarm Message Regex field, enter the Regular Expression (RegEx) that will match the text of the alarm. The RegEx value must meet the following criteria:
|
|
Alarm Table Match |
Optional: Enter the RealTime database (RTDB) table name. Note: If you plan on using this almSevOverride record to match a system alarm, enter SYSTEM. |
|
Alarm Process Match |
Optional: Enter the AVEVA Enterprise SCADA process name. Note: It is strongly advised to specify either a RTDB table or an AVEVA Enterprise SCADA process for each record to limit the scope. |
|
Alarm Host Match |
Optional: Enter the AVEVA Enterprise SCADA process name. |