AVEVA Enterprise SCADA

Enable data quality

  • Last UpdatedApr 24, 2025
  • 2 minute read

RealTime record fields can be added as items to the Open Platform Communications (OPC) client program connected to the OPC server. You can configure the data quality to be returned as the quality of the connection or the quality of the data value.

For any analog, status, rate, or tank telemetered field added as an item to the OPC client, you can configure the OPC server to return the data quality as:

  • The quality of the connection between the AVEVA Enterprise SCADA OPC server and the PubSub Service for that point, or

  • The quality of the data value itself, as determined from the record's flag structure.

Once the OPC client receives the data and quality, it must display and/or process the quality.

Notes: If the connection between the OPC server and the PubSub Service for a given point failed, the data quality for that point is NOT-CONNECTED, regardless of the data quality of the point. For example, if you delete or remove a point added as an item to an OPC client, the system marks the quality as NOT-CONNECTED for that point.

Because the OPC server provides its own data quality, ensure that you do not use the Quality Bit field on the Input tab of the Row Edit dialog boxes for the RealTime database (RTDB) records corresponding to the analog or rate points. Otherwise, the values and data quality for those analog or rate points may not be as expected.

If enabled, the system provides the actual data quality of the following telemetered records:

Table

Point

Analog

curval

Status

cursta

cursta@raw

Rate

curate

acccur

Tank

field.volume

field.num_inc

currentGO.volume

currentGO.num_inc

currentGS.volume

currentGS.num_inc

flevel

GOflow_rate

GSflow_rate

Multistate

inputCurRaw