AVEVA Enterprise SCADA

Gasmeter table details

  • Last UpdatedApr 24, 2025
  • 2 minute read

The gasmeter table contains information on the system’s gas meters. Only fields specific to RealTime operation are available for editing in the Advanced Database Editor (ADE). The table is initially populated via AVEVA Measurement Advisor. The gasmeter table contains the following internal fields:

Internal Field Name

Data Type

Description

ContractHour

GasC_ContractHr

The contract hour for this gas meter.

creep.devlim

float

An alarm is generated when a gas meter value becomes greater than the initial setpoint value plus the creep value, or less than the initial setpoint value minus the creep value.

creep.doit

oas_boolean_t

Set an alarm to detect when the gas meter creeps out of the normal calibrated state over time?

dataset

doas_dset_slot

This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record.

DataSource

GasM_DataSource

The gas meter type.

description

description

A description of this gasmeter point, up to 47 characters in length.

displayOrder

int

This field is used by Display Framework, a separately acquired product.

flag

flags

For information on the flag structure, see Flag structure details.

group

groupslot

This field shows the group that this point is associated with for alarming.

hilow.dead

float

This value controls the sensitivity of the high and low alarms.

hilow.doithi

oas_boolean_t

Perform a High alarm check?

hilow.doithihi

oas_boolean_t

Perform a HighHigh alarm check?

hilow.doitlo

oas_boolean_t

Perform a Low alarm check?

hilow.doitlolo

oas_boolean_t

Perform a LowLow alarm check?

hilow.doitroc

oas_boolean_t

Enable the Rate of Change (ROC) alarm?

hilow.hilim

float

The High alarm limit threshold.

hilow.hihilim

float

The HighHigh alarm limit threshold.

hilow.lolim

float

The Low alarm limit threshold.

hilow.lololim

float

The LowLow alarm limit threshold.

hilow.roclim

float

An alarm is generated if the calculated ROC is greater than this amount.

name

pntname

The unique name of this gasmeter record. The name can be up to 32 characters in length.

rtu

remoteslot

The remote associated with this gas meter.

runNumber

short

The run number for this gas meter (read-only).

tstampPref

GasC_TStampPref

The local timestamp preference.

wellunit

pntname

This field is used by Display Framework, a separately acquired product.